SRI PRECONFIGURED GC SYSTEMS - TRANSFORMER OIL GAS ANALYZER (TOGA) GC

 
SRI PRECONFIGURED GCs
SRI ACCESSORIES
SRI DETECTORS
SRI INJECTORS
SRI GC MAINFRAMES
SRI TOGA GC
HID, FID and/or TCD detectors
10-port gas sampling valve and valve oven
Gas extraction loop
Peaksimple data system
Built-in standards preparation module

By analyzing the gases dissolved in transformer oil, potential transformer faults can be avoided. ASTM D3612 provides for identification and quantification of dissolved gases in transformer oil by GC. The SRI TOGA GC uses the version referred to as D3612B, the direct injection technique where the dissolved gas extraction takes place inside the GC. This means that other than collecting the transformer oil in a glass airtight syringe, no sample preparation is necessary prior to injection into the TOGA GC.

To achieve the TOGA analysis, transformer oil is pumped through the gas extraction loop of a TOGA GC equipped with HID or HID/TCD detectors. The TCD is  used to quantify the oxygen and nitrogen because the HID is too sensitive for the large quantities typically found dissolved in transformer oil.

In the TOGA GC, the transformer oil sample is injected by peristaltic pump through a unique gas extraction loop. The gas extraction loop consists of permeation membrane tubing encapsulated in a trap-heated glass tube. The permeation tubing is plumbed to the sample inlet, the dual 10-port valves, and the waste/sample outlet. Solenoid valves are included for purging the gas extraction chamber with helium between runs.

The presence and quantities of certain gases in the transformer oil indicate four broad types of possible general fault conditions:

1-Transformer oil overheating: methane, ethane, ethylene, and small quantities of acetylene
2-Partial Discharge: hydrogen, methane, and small quantities of acetylene and ethane
3-Sustained Arcing: hydrogen, acetylene, and ethylene
4-Insulating Paper Overheating: carbon monoxide and carbon dioxide

#SRI-8610-0031-1, TOGA GC WITH HID (110V)

$17,495.00

#SRI-8610-0031-2, TOGA GC WITH HID (220V)

$17,495.00

#SRI-8610-0032-1, TOGA GC WITH TCD/HID (110V)

$20,495.00

#SRI-8610-0032-2, TOGA GC WITH TCD/HID (220V)

$20,495.00
Options & Upgrades: additional detectors, 6 channel USB PeakSimple data system
 